Junior Engineer • 2024 • Paper-I (Electrical Engineering)

Copper conductors are generally not used for transmission lines because -

A) it is costly
B) it is not strong enough to allow long spans
C) it requires more support
D) it requires more insulation
In the design of overhead transmission lines, the primary goal is to achieve a balance between electrical efficiency and economic viability. 1. **Cost Analysis (Option a):** Copper has excellent electrical conductivity (higher than aluminum), but it is significantly more expensive than aluminum. For long-distance transmission lines involving thousands of kilometers of cabling, the cost of copper would be prohibitively high, making it economically unfeasible. 2. **Strength and Weight (Option b & c):** While copper is denser and heavier than aluminum (which would technically require more support or shorter spans if the same cross-sectional area were used), the industry solves this by using ACSR (Aluminum Conductor Steel Reinforced) cables. ACSR provides the high tensile strength of steel with the conductivity of aluminum. The primary deterrent for copper, however, remains the raw material cost. 3. **Insulation (Option d):** Insulation requirements depend on the operating voltage of the line, not the material of the conductor. Copper and aluminum conductors of the same voltage rating require the same amount of insulation. Therefore, the dominant reason copper is not used for long-distance transmission lines is its high cost relative to aluminum.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

In the ring main distribution system, the distribution network is fed usually -

A) by one feeder
B) by two feeders
C) at different points
D) by four feeders
In a Ring Main Distribution system, the distribution transformer or the main distribution line forms a closed loop (ring). This ring is typically fed by two independent feeders from two different substations (or two different feeders from the same substation). 1. **Reliability**: The primary advantage of this system is reliability. If a fault occurs on one section of the ring or if one feeder fails, the power can still reach all consumers via the other feeder and the remaining healthy part of the ring. 2. **Continuity of Supply**: Because it is fed by two feeders, the system ensures that there is no complete blackout for any consumer during a single point of failure in the feeder line. Comparing with other options: - **Option a (one feeder)**: This describes a Radial Distribution system, which is less reliable because a fault at any point results in power loss for all subsequent consumers. - **Option c (at different points)**: While power is distributed to consumers at different points along the ring, the 'feeding' of the network itself is done by the feeders. - **Option d (four feeders)**: This is not a standard configuration for a basic ring main system and would be unnecessarily expensive and complex for typical distribution needs.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

The pH value of pure water is -

A) zero
B) 1
C) 7
D) infinite
The pH value is a measure of the acidity or alkalinity of a solution, defined as the negative logarithm (base 10) of the molar concentration of hydrogen ions [H+]. In pure water, water molecules undergo self-ionization: H2O ⇌ H+ + OH-. At standard room temperature (25°C), the concentration of hydrogen ions [H+] and hydroxide ions [OH-] are equal, both being 10^-7 mol/L. Therefore, pH = -log[10^-7] = 7. A pH of 7 is considered neutral, meaning the solution is neither acidic nor basic. Analysis of options: - Option (a) 'zero' would indicate an extremely strong acid. - Option (b) '1' would indicate a strongly acidic solution. - Option (c) '7' is the correct value for neutral pure water at 25°C. - Option (d) 'infinite' is physically impossible on the standard pH scale (which typically ranges from 0 to 14).
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

For protection of rotating machines against lightning surges is used.

A) lightning arrester
B) capacitor
C) combination of lightning arrester and capacitor
D) lightning conductor and arrester
Rotating machines (such as generators and motors) are susceptible to high-voltage transients caused by lightning surges entering through the power lines. To protect the winding insulation of these machines from breakdown due to such overvoltages, a lightning arrester (also known as a surge diverter) is used. A lightning arrester provides a low-impedance path to the ground when a high-voltage surge occurs, effectively diverting the surge current away from the machine's windings and limiting the voltage to a safe level. Analysis of other options: - b. Capacitor: Capacitors are used for power factor correction or filtering, not for diverting high-voltage lightning surges. - c. Combination of lightning arrester and capacitor: While capacitors can be used in surge filters, the primary device for lightning protection is the arrester itself. - d. Lightning conductor and arrester: A lightning conductor (air terminal) is used to protect the structure/building from direct strikes, whereas a lightning arrester is used to protect the electrical equipment/insulation from surges traveling through the lines. For the specific protection of the machine's internal electrical components, the arrester is the correct device.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

If the span of transmission increased, the sag -

A) decreases
B) increases
C) remains the same
D) decreases two times
The sag (S) of a transmission line conductor is the vertical distance between the lowest point of the conductor and the straight line joining its supports. For a conductor supported at equal levels, the formula for sag is given by: S = (W * L²) / (8 * T), where W is the weight per unit length of the conductor, L is the span length (distance between supports), and T is the tension in the conductor. From this formula, it is evident that Sag (S) is directly proportional to the square of the span length (S ∝ L²). Therefore, if the span (L) increases, the sag (S) will increase significantly. Option (a) is incorrect because sag increases, not decreases. Option (c) is incorrect because sag is dependent on the span length. Option (d) is incorrect because the relationship is quadratic (square), not a simple linear factor of two.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

The minimum ground clearance of the lowest conductor 11kV voltage lines along the street -

A) 4m
B) 5m
C) 5.80m
D) 7.591 m
According to the Indian Electricity Rules (IE Rules), specifically Rule 80, the minimum ground clearance for overhead lines is specified based on the voltage level and the location of the line. For high voltage lines (up to 33kV) crossing or running along a street, the minimum vertical clearance from the surface of the street to the lowest conductor is mandated to be 5.8 meters. Breakdown of clearances for 11kV lines: 1. Along a street: 5.8 meters (Correct option c). 2. Across a street: 5.8 meters. 3. Over any other area (non-street): 4.6 meters. Comparing the options: - Option (a) 4m: Too low for street clearance; does not meet safety standards for 11kV. - Option (b) 5m: Below the statutory requirement of 5.8m. - Option (d) 7.591m: This is higher than the minimum requirement and is not the standard minimum specified in the rules.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

The type of turbine used in hydro power plant between 10-70m is -

A) Pelton
B) Kaplan
C) Francis
D) Propeller
Hydroelectric turbines are selected based on the 'head' (the vertical distance the water falls). 1. **Pelton Wheel (Impulse Turbine):** Used for high heads, typically above 300m (though can go lower to 100m). It converts the kinetic energy of a high-velocity jet into mechanical energy. 2. **Francis Turbine (Reaction Turbine):** This is a mixed-flow turbine used for medium heads. The typical operating range is between 30m and 600m, but it is the primary choice for the 10m to 70m range mentioned in the question, as it bridges the gap between low-head and high-head turbines. 3. **Kaplan/Propeller Turbines (Reaction Turbines):** These are axial-flow turbines used for low heads, typically below 30m. While Kaplan turbines can operate in the 10-30m range, the Francis turbine is the standard answer for the broader medium-head category often cited in technical exams for this specific range. Comparing the options, the Francis turbine is the most versatile and correct choice for the specified medium-head range of 10-70m.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

Trash racks are located -

A) near tailrace
B) at the entrance of turbine
C) inside penstock
D) at the intake
Step-by-step reasoning: 1. **Definition of Trash Racks**: Trash racks are metallic screens or grids placed at the entry point of water into a hydroelectric system. 2. **Purpose**: Their primary function is to prevent floating debris (such as logs, leaves, ice, and plastic) from entering the water conveyance system (intake, penstock, and turbine). 3. **Placement**: To protect the entire downstream infrastructure, they must be placed at the very beginning of the water path, which is the **intake**. 4. **Analysis of Options**: - (a) **Near tailrace**: The tailrace is where water exits the plant; placing a rack here would be useless for protecting the machinery. - (b) **At the entrance of turbine**: While some small strainers might exist, the primary trash racks are placed much earlier to prevent the penstock from clogging. - (c) **Inside penstock**: Placing racks inside the penstock would be impractical for cleaning and would not prevent debris from entering the pipe itself. - (d) **At the intake**: This is the correct location to filter water before it enters the penstock and turbine.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

Minimum distance of underground cable from the foundation of building should be -

A) 100cm
B) 50cm
C) 10cm
D) 5cm
According to standard electrical installation practices and safety codes (such as those derived from IS codes and general wiring regulations for domestic and industrial installations), underground cables must be laid at a safe distance from the foundation of a building to prevent mechanical stress on the cable due to soil settlement or structural pressure. The recommended minimum horizontal distance of an underground cable from the foundation of a building is 50 cm. This ensures that any future excavation or structural repairs to the foundation do not accidentally damage the cable, and conversely, that the cable's heat dissipation does not affect the foundation materials. Options a (100cm) is generally more than the minimum requirement, while options c (10cm) and d (5cm) are dangerously close and provide no protection against structural movement or accidental damage.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

The primary function of a lightning arrester is to:

A) divert lightning current safely to ground
B) increase the voltage level in a power system
C) acts as a fuse to interrupt excess current
D) store electrical energy for later use
A lightning arrester (also known as a surge arrester) is a protective device used in electrical power systems to protect equipment from the damaging effects of lightning strikes and switching surges. 1. **How it works**: Under normal operating voltage, the arrester acts as an insulator (high impedance). However, when a high-voltage surge (like lightning) hits the line, the arrester's impedance drops rapidly, providing a low-resistance path to the earth. 2. **Primary Function**: By providing this low-impedance path, it 'diverts' the massive current of the lightning strike safely to the ground, preventing the surge from entering and destroying sensitive equipment like transformers. **Analysis of other options:** - **Option b**: Increasing voltage is the function of a step-up transformer, not a protection device. - **Option c**: A fuse is designed to melt and break the circuit during an overcurrent or short-circuit condition; a lightning arrester does not 'interrupt' the current by breaking the circuit but rather redirects it. - **Option d**: Storing electrical energy is the function of capacitors or batteries.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

Fault location in indoor type substation is -

A) easy
B) difficult
C) dependent on type of fault
D) independent on type of fault
In an indoor substation, the electrical equipment (such as switchgear, busbars, and transformers) is housed within a building or enclosed compartments. Unlike outdoor substations, where faults (like flashovers or physical damage) are often visible to the naked eye upon inspection, indoor faults are concealed within panels, conduits, or enclosures. This lack of direct visibility makes the physical identification and location of the fault significantly more difficult and time-consuming, often requiring specialized testing equipment and the dismantling of panels to find the exact point of failure. Therefore, fault location in indoor substations is considered 'difficult' compared to outdoor substations.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

Which gas is used in gas insulated substation?

A) Nitrogen + SF6
B) Hydrogen + SF6
C) SF6
D) None of these
A Gas Insulated Substation (GIS) uses a specific gas to insulate the high-voltage components, allowing the equipment to be placed much closer together than in an Air Insulated Substation (AIS). The gas used is Sulfur Hexafluoride (SF6). SF6 is preferred because it has excellent dielectric strength (approximately 2.5 to 3 times that of air), is chemically stable, non-flammable, and has superior arc-quenching properties, which makes it ideal for high-voltage circuit breakers and switchgear. Analysis of options: - Option (a) and (b): While Nitrogen is sometimes used for purging or as a secondary gas in specific applications, the primary insulating and arc-quenching medium that defines a GIS is SF6. Hydrogen is not used as a primary insulator in GIS. - Option (c): SF6 is the industry standard for GIS due to its high electronegativity, which allows it to absorb free electrons and extinguish arcs quickly.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

LVDT is always used as -

A) secondary transducer
B) primary transducer
C) primary signal generator
D) secondary signal generator
To understand why an LVDT (Linear Variable Differential Transformer) is classified as a secondary transducer, it is important to distinguish between primary and secondary transducers in a measurement system: 1. **Primary Transducer**: This is the first element in a sensing system that converts a physical quantity (like pressure, force, or temperature) into a mechanical displacement or a different physical form. For example, a Bourdon tube converts pressure into a mechanical displacement. 2. **Secondary Transducer**: This device takes the output of the primary transducer (usually a mechanical displacement) and converts it into an electrical signal (voltage or current). **Application to LVDT**: An LVDT does not directly measure the original physical quantity (like pressure or force). Instead, it measures the **linear displacement** of its internal core. In a typical industrial setup, a primary transducer (like a diaphragm or bellows) first converts the measured variable into a displacement, and the LVDT then converts that displacement into an electrical signal. Therefore, the LVDT acts as the secondary stage of transduction. **Analysis of Options**: - **Option a (Correct)**: LVDT converts mechanical displacement (the output of a primary transducer) into an electrical signal, making it a secondary transducer. - **Option b (Incorrect)**: A primary transducer converts the raw physical quantity into displacement; the LVDT requires displacement as its input. - **Option c & d (Incorrect)**: 'Signal generator' refers to devices that create a waveform (like a function generator), whereas an LVDT is a sensor/transducer that responds to an external stimulus.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

In a transmission line, if the load is suddenly increased in the receiving end of the system, the phase shift will -

A) decrease
B) becomes zero
C) increase
D) not be affected
In a power transmission system, the real power (P) transferred from the sending end to the receiving end is governed by the power flow equation: P = (V_s * V_r / X) * sin(δ), where V_s is the sending end voltage, V_r is the receiving end voltage, X is the line reactance, and δ is the power angle (the phase shift between the sending end voltage and the receiving end voltage). 1. When the load at the receiving end is suddenly increased, the demand for real power (P) increases. 2. Since V_s, V_r, and X are relatively constant (or change minimally compared to the power demand), the only way for the system to transmit more power is for the value of sin(δ) to increase. 3. For an increase in sin(δ), the angle δ (the phase shift) must increase. Therefore, as the load increases, the receiving end voltage lags further behind the sending end voltage, leading to an increase in the phase shift. - Option (a) is incorrect because a decrease in phase shift would result in less power being transmitted. - Option (b) is incorrect because a zero phase shift implies no real power is being transferred. - Option (d) is incorrect because the power angle is directly dependent on the load current and power flow.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

FM broadcast band lies in -

A) VHF band
B) UHF band
C) SHF band
D) HF band
Step-by-step reasoning: 1. **Identify the FM Broadcast Band**: Standard commercial FM radio broadcasting typically operates in the frequency range of 88 MHz to 108 MHz. 2. **Analyze the Radio Frequency Spectrum**: - **HF (High Frequency)**: 3 MHz to 30 MHz. - **VHF (Very High Frequency)**: 30 MHz to 300 MHz. - **UHF (Ultra High Frequency)**: 300 MHz to 3 GHz. - **SHF (Super High Frequency)**: 3 GHz to 30 GHz. 3. **Comparison**: Since the FM broadcast range (88–108 MHz) falls squarely within the 30 MHz to 300 MHz range, it is classified as part of the VHF band. 4. **Evaluating Options**: - Option (a) VHF band: Correct. - Option (b) UHF band: Incorrect; used for digital TV and mobile phones. - Option (c) SHF band: Incorrect; used for satellite communications and radar. - Option (d) HF band: Incorrect; used for shortwave radio.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

As matter of economy, voltage for power transmission will be -

A) low
B) high
C) medium
D) very low
In power transmission, the primary goal for economy is to minimize power losses and reduce the cost of conductor material. 1. Power Loss: The power loss in a transmission line is given by the formula P_loss = I²R, where 'I' is the current and 'R' is the resistance of the line. 2. Power Equation: The total power transmitted is P = V * I * cos(φ). For a constant amount of power (P), if the voltage (V) is increased, the current (I) decreases proportionally. 3. Impact of High Voltage: Since power loss depends on the square of the current (I²), reducing the current by increasing the voltage significantly reduces the energy lost as heat. 4. Material Economy: Lower current allows for the use of thinner conductors (smaller cross-sectional area), which reduces the amount of copper or aluminum required, thereby lowering the capital cost of the transmission line. Therefore, to ensure maximum economy and efficiency, power is transmitted at high voltages.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

In our home, the electrical appliances are connected -

A) in parallel with the source only if it is a high power appliance
B) in series with the source
C) some in series and some in parallel with the source
D) in parallel with the source
In domestic wiring, all electrical appliances are connected in parallel for the following technical reasons: 1. Constant Voltage: In a parallel circuit, every appliance receives the full supply voltage (e.g., 230V in India), which is necessary for them to operate at their rated power. 2. Independent Operation: Each appliance has its own dedicated path to the source. This means you can turn one appliance (like a light bulb) ON or OFF without affecting the operation of other appliances (like a refrigerator). 3. Fault Tolerance: If one appliance fails or a bulb burns out, the circuit for other appliances remains closed, and they continue to function normally. Why other options are incorrect: - Option (b) 'in series': If connected in series, the voltage would be divided among all appliances, meaning none would receive enough voltage to work properly. Furthermore, if one appliance failed, the entire circuit would break, and everything in the house would turn off. - Option (a) and (c): These are incorrect because the requirement for constant voltage and independent control applies to all appliances, regardless of whether they are high-power or low-power.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

The economic size of a conductor is determined by -

A) Kirchhoff’s law
B) Ohm’s law
C) Kelvin’s law
D) Faraday’s law
The economic size of a conductor (the optimal cross-sectional area) is determined using Kelvin's Law. Kelvin's Law states that the most economical conductor size is that for which the annual cost of interest and depreciation on the conductor is equal to the annual cost of energy wasted (I²R loss) in that conductor. Here is why the other options are incorrect: - Kirchhoff's laws (a) are used for analyzing complex electrical circuits (KCL and KVL). - Ohm's law (b) defines the relationship between voltage, current, and resistance (V=IR). - Faraday's law (d) relates to electromagnetic induction and the generation of EMF in a conductor. Therefore, for the specific purpose of balancing capital expenditure (cost of material) versus operational expenditure (cost of power loss), Kelvin's Law is the standard engineering principle applied.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

A piezometer may not be used for pressure measurement in pipes -

A) when the pressure difference is high
B) when the velocity is high
C) when the fluid in the pipe is gas
D) when the fluid in the pipe is highly viscous
A piezometer is the simplest form of manometer, consisting of a vertical tube open to the atmosphere. It works on the principle that the liquid rises in the tube until the hydrostatic pressure equals the pressure in the pipe (p = ρgh). 1. Why Option (c) is correct: A piezometer requires the fluid to form a distinct, stable free surface (meniscus) open to the atmosphere to measure the height (h). Gases are compressible and expand to fill the entire volume of the tube; they do not form a stable liquid-like free surface that can be measured as a height. Therefore, a piezometer cannot be used to measure gas pressure. 2. Why Option (a) is incorrect: While high pressure makes a piezometer impractical (because the tube would need to be impractically tall), it is technically possible to use one if the tube is long enough. However, the inability to measure gas is a fundamental physical limitation, not just a practical one. 3. Why Option (b) is incorrect: Piezometers measure static pressure. While high velocity creates dynamic pressure, a piezometer installed perpendicular to the flow measures the static pressure regardless of the velocity. 4. Why Option (d) is incorrect: High viscosity may slow down the response time (the time it takes for the fluid to reach the equilibrium height), but it does not prevent the piezometer from functioning.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

The picture on an oscilloscope screen is produced by -

A) an electron beam
B) a moving vane
C) a T-V type camera
D) an intensity control
An oscilloscope (specifically the analog type) utilizes a Cathode Ray Tube (CRT) to visualize electrical signals. Inside the CRT, a heated cathode emits a stream of electrons, forming an electron beam. This beam is accelerated and focused toward a fluorescent screen. Deflection plates (horizontal and vertical) steer the beam across the screen based on the input voltage signals. When the electron beam strikes the phosphor-coated screen, the phosphor fluoresces, creating a visible spot of light that traces the waveform of the signal. Why other options are incorrect: - b. A moving vane: This is typically associated with mechanical meters (like a PMMC instrument), not an oscilloscope screen. - c. A T-V type camera: A camera captures an image; it does not produce the image on the oscilloscope screen. - d. An intensity control: Intensity control is a setting used to adjust the brightness of the beam, but it is not the mechanism that produces the picture itself.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

A circuit breaker perform the function of -

A) detection only
B) circuit interruption only
C) both deduction and circuit interruption
D) circuit rectification
A circuit breaker is a mechanical switching device capable of making, carrying, and breaking currents under normal circuit conditions, and also breaking currents under specified abnormal conditions (such as a short circuit). Its primary and sole function is the 'interruption' or 'breaking' of the electrical circuit to protect the system. To clarify the distinction between detection and interruption: 1. Detection: The function of detecting a fault (overcurrent or short circuit) is performed by a 'Relay'. The relay senses the abnormality and sends a trip signal to the circuit breaker. 2. Interruption: Upon receiving the signal from the relay, the circuit breaker physically opens its contacts to interrupt the current flow. Therefore: - Option (a) is incorrect because detection is the job of the relay. - Option (c) is incorrect because the circuit breaker does not 'detect' the fault itself; it acts upon the detection performed by a relay. - Option (d) is incorrect because rectification is the process of converting AC to DC, which is performed by a rectifier, not a circuit breaker.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

The lightning arrester is connected -

A) in series with the line
B) between line and Earth
C) to a pole near the line
D) to circuit breaker
A lightning arrester (also known as a surge arrester) is a protective device used to protect electrical power equipment from the damaging effects of lightning strikes and switching surges. 1. **Working Principle**: Under normal operating voltage, the lightning arrester acts as an insulator (high impedance), preventing current from flowing to the ground. However, when a high-voltage surge (like lightning) hits the line, the arrester's impedance drops sharply, allowing the surge current to be safely diverted to the Earth. 2. **Connection**: To divert the surge away from the expensive equipment (like transformers), the arrester must be connected in parallel between the phase conductor (line) and the ground (Earth). 3. **Analysis of Options**: - **Option (a)**: If connected in series, it would block the normal flow of power to the load. - **Option (b)**: Correct. This provides a low-impedance path to ground only during over-voltage conditions. - **Option (c)**: Simply being 'near' the line is insufficient; it must be electrically connected to the line to divert the surge. - **Option (d)**: While it protects the circuit breaker and other equipment, it is not connected 'to' the breaker as its primary functional connection; it is connected between the line and earth.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

Residential load is connected between -

A) any two phase
B) any one phase and neutral
C) any two phase and neutral
D) three phase
In electrical power distribution, residential loads are typically single-phase loads. In a standard three-phase, four-wire distribution system (the most common system for residential areas), power is delivered as a combination of one phase (live wire) and a neutral wire. This provides the standard single-phase voltage (e.g., 230V in India or 120V in the US) required for household appliances like lights, fans, and televisions. Analysis of other options: - Option (a) 'any two phase' would provide a line-to-line voltage (e.g., 400V or 415V), which is too high for standard residential appliances and would cause them to burn out. - Option (c) 'any two phase and neutral' is not a standard connection for a single residential load. - Option (d) 'three phase' is used for heavy industrial loads or large commercial equipment (like large AC plants or industrial motors), not for general residential household loads.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

Thermistor have -

A) high and negative temperature coefficient
B) low and negative temperature coefficient
C) high and positive temperature coefficient
D) low and positive temperature coefficient
A thermistor (thermal resistor) is a type of semiconductor resistor whose resistance is strongly dependent on temperature. Most common thermistors are NTC (Negative Temperature Coefficient) thermistors. 1. **Negative Temperature Coefficient (NTC):** In NTC thermistors, as the temperature increases, the electrical resistance decreases. This happens because the increase in thermal energy releases more charge carriers (electrons and holes) in the semiconductor material, increasing conductivity. 2. **High Coefficient:** Unlike metals (like Platinum in RTDs), which have a very small and linear change in resistance per degree Celsius, thermistors exhibit a very large (high) change in resistance for a small change in temperature. This makes them highly sensitive sensors. Comparing the options: - Option (a) is correct because thermistors typically have a high sensitivity (high coefficient) and an inverse relationship between resistance and temperature (negative coefficient). - Option (b) is incorrect because the coefficient is high, not low. - Options (c) and (d) are generally incorrect for standard thermistors, although PTC (Positive Temperature Coefficient) thermistors exist, the defining characteristic of the general 'thermistor' used in instrumentation for temperature sensing is the high NTC property.
Junior Engineer • 2024 • Paper-I (Electrical Engineering)

MCCB stands for -

A) Miniature Current Circuit Breaker
B) Maximum Current Circuit Breaker
C) Moulded Cabinet Circuit Breaker
D) Moulded Case Circuit Breaker
MCCB stands for Moulded Case Circuit Breaker. It is an electrical protection device used to protect electrical circuits from excessive current, which can arise from overloads or short circuits. The term 'Moulded Case' refers to the fact that the breaker's internal components (contacts, arc chutes, and trip mechanisms) are enclosed in a durable, insulating moulded plastic or composite housing. Analysis of other options: - Option (a) 'Miniature Current Circuit Breaker' is incorrect; while MCBs exist, they are called Miniature Circuit Breakers, not 'Current' circuit breakers. - Option (b) 'Maximum Current Circuit Breaker' is a fabricated term and does not exist in standard electrical engineering terminology. - Option (c) 'Moulded Cabinet Circuit Breaker' is incorrect; the enclosure is a 'case' for the specific device, not a 'cabinet' (which usually refers to the larger panel housing multiple devices).