← MES Jr. Grade

Past Questions

MES Jr. Grade • 2024 • Paper-II

Which of the following single phase motors will operate at high power factor?

A) Shaded pole motor
B) Capacitor run motor
C) Split phase motor
D) Capacitor start motor
To understand why the Capacitor run motor operates at a high power factor, we must look at the phase relationship between voltage and current in single-phase induction motors. 1. **Single Phase Induction Motors** are inherently inductive loads, meaning the current lags the voltage, resulting in a low power factor. 2. **Capacitor Run Motors (Permanent Split Capacitor - PSC)**: In these motors, a capacitor is connected in series with the auxiliary winding and remains in the circuit during both starting and running. The capacitor creates a leading current in the auxiliary winding. This leading current partially cancels out the lagging current of the main winding. The net result is a reduction in the total lagging current, which shifts the overall power factor closer to unity (higher power factor). **Analysis of other options:** - **Shaded Pole Motor (a):** These have very low starting torque and very poor power factor and efficiency due to the high leakage reactance of the shading coil. - **Split Phase Motor (c):** These rely on the inherent resistance and inductance difference between the main and start windings. Once started, the main winding (highly inductive) dominates, leading to a low running power factor. - **Capacitor Start Motor (d):** The capacitor is used only for starting and is disconnected by a centrifugal switch once the motor reaches a certain speed. Therefore, during the 'run' phase, it behaves like a split-phase motor with a low power factor.
MES Jr. Grade • 2024 • Paper-II

A DC shunt generator delivers 95 A at 250 V and the resistance of the shunt field and armature are 50Ω and 0.05Ω respectively. The generated emf will be

A) 270V
B) 265V
C) 255V
D) 275V
To find the generated emf (Eg) of a DC shunt generator, we follow these steps: 1. **Identify Given Data:** - Load Current (IL) = 95 A - Terminal Voltage (V) = 250 V - Shunt Field Resistance (Rsh) = 50 Ω - Armature Resistance (Ra) = 0.05 Ω 2. **Calculate Shunt Field Current (Ish):** In a shunt generator, the field winding is in parallel with the load. Ish = V / Rsh = 250 V / 50 Ω = 5 A 3. **Calculate Armature Current (Ia):** The armature current is the sum of the load current and the shunt field current. Ia = IL + Ish = 95 A + 5 A = 100 A 4. **Calculate Generated EMF (Eg):** The generated emf must cover the terminal voltage and the voltage drop across the armature resistance. Eg = V + (Ia × Ra) Eg = 250 V + (100 A × 0.05 Ω) Eg = 250 V + 5 V = 255 V Therefore, the generated emf is 255V, which corresponds to option (c). Options (a), (b), and (d) are incorrect as they do not match the calculated value based on the given parameters.
MES Jr. Grade • 2024 • Paper-II

The complex conjugate poles of a transfer function lie on the left half of the s-plane, the system is

A) stable
B) marginally stable
C) unstable
D) may be stable or unstable
In control system theory, the stability of a linear time-invariant (LTI) system is determined by the location of the poles of its transfer function in the s-plane. 1. **Stable System**: A system is considered absolutely stable if all poles of the transfer function lie strictly in the Left Half of the s-plane (LHP). This ensures that the impulse response of the system decays to zero as time approaches infinity (e.g., terms like e^(-at) where a > 0). 2. **Marginally Stable System**: A system is marginally stable if there are non-repeated poles on the imaginary axis (jω-axis) and no poles in the Right Half Plane (RHP). This results in sustained oscillations. 3. **Unstable System**: A system is unstable if at least one pole lies in the Right Half Plane (RHP) or if there are repeated poles on the imaginary axis. This leads to an exponentially growing response. In this specific question, it is stated that the complex conjugate poles lie on the left half of the s-plane. Since all poles are in the LHP, the system is stable.
MES Jr. Grade • 2024 • Paper-II

Which of the following power plant takes least time in starting from cold condition to full load condition?

A) Nuclear power plant
B) Thermal power plant
C) Hydroelectric power plant
D) Gas power plant
The time required for a power plant to go from a cold start (completely shut down) to full load is known as the 'start-up time'. 1. **Hydroelectric Power Plant (Option c):** These plants have the fastest start-up time. Since they rely on the potential energy of water, starting the plant simply involves opening the gates/valves to allow water to flow through the turbine. This process takes only a few minutes, making them ideal for peak load demands and emergency backup. 2. **Gas Power Plant (Option d):** Gas turbines are relatively fast (faster than thermal or nuclear) because they don't require boiling water to create steam, but they still take longer than hydroelectric plants to reach full operational stability. 3. **Thermal Power Plant (Option b):** These plants require a significant amount of time to heat the boiler and generate high-pressure steam to drive the turbine. This process can take several hours to a day to avoid thermal stress on the components. 4. **Nuclear Power Plant (Option a):** These have the longest start-up times due to the complex process of initiating and controlling the nuclear fission chain reaction and the gradual heating of the coolant/steam cycle to prevent structural damage. Therefore, the hydroelectric power plant takes the least time to reach full load from a cold condition.
MES Jr. Grade • 2024 • Paper-II

What is an element in an electrical circuit which serves as a protection against overload?

A) Fuse
B) Mica
C) Resistor
D) Semiconductor
A fuse is a safety device designed to protect an electrical circuit from overcurrent or overload. It consists of a metal strip or wire that melts when too much current flows through it, thereby breaking the circuit and preventing damage to the wiring or connected appliances. Analysis of other options: - b. Mica: This is an insulating mineral used primarily as a dielectric in capacitors or as an insulator in high-voltage equipment; it does not provide overload protection. - c. Resistor: This is a passive component used to create resistance in the flow of current to achieve a desired voltage drop or limit current; it is not a protection device. - d. Semiconductor: This is a material (like Silicon or Germanium) used to create components like diodes and transistors for switching or amplification; it is not inherently a circuit protection device against overload.
MES Jr. Grade • 2024 • Paper-II

The current zero interruption, in oil and air blast circuit breakers is achieved by

A) lengthening of the gap between the contact terminals
B) cooling and blast effect
C) deionizing the oil with forced air
D) both (a) & (b)
In circuit breakers, 'current zero interruption' refers to the process of extinguishing the arc that forms when contacts separate at the moment the alternating current passes through zero. To prevent the arc from re-striking (re-igniting), the dielectric strength of the gap must be increased faster than the recovery voltage. 1. Lengthening of the gap (Option a): By increasing the distance between the contact terminals, the electric field intensity is reduced, and the physical path for the arc is increased, which helps in breaking the conduction path. 2. Cooling and blast effect (Option b): In Oil Circuit Breakers (OCB), the arc decomposes the oil into hydrogen gas, which creates a high-pressure 'blast' that pushes the arc away and cools it. In Air Blast Circuit Breakers (ABCB), a high-velocity stream of compressed air is used to physically blow the arc away and cool the ionized gases rapidly. Since both the physical separation (lengthening the gap) and the active removal/cooling of ionized particles (blast effect) are essential mechanisms to achieve successful interruption in these specific types of breakers, option (d) is the correct choice.
MES Jr. Grade • 2024 • Paper-II

Which condition is correct for a salient pole rotor machine?

A) Small diameter and small axial length
B) Small diameter and long axial length
C) Large diameter and large axial length
D) Large diameter and small axial length
In electrical machine design, there are two primary types of rotor constructions for synchronous machines: Salient Pole and Cylindrical (Non-salient) rotors. 1. **Salient Pole Rotors**: These rotors have poles that project out from the surface. To accommodate a large number of poles (which is necessary for low-speed operation, typically driven by hydraulic turbines), the rotor must have a **large diameter**. Because the poles project outwards, the rotor is mechanically unstable if it is too long due to centrifugal forces and structural constraints; therefore, it is designed with a **small axial length**. This results in a 'disc-like' appearance. 2. **Cylindrical Rotors**: These are used in high-speed machines (like steam turbines). To withstand high centrifugal forces and reduce windage loss, they are designed with a **small diameter** and a **long axial length** to maintain the required volume of copper and iron. Comparing the options: - Option (a) and (b) describe small diameters, which are characteristic of cylindrical rotors. - Option (c) is incorrect because a large axial length combined with a large diameter would be mechanically impractical and inefficient for a salient pole machine. - Option (d) correctly identifies the physical characteristics of a salient pole rotor: Large diameter (to fit multiple poles) and small axial length (for mechanical stability).
MES Jr. Grade • 2024 • Paper-II

If the fault current is 2000 A, the relay setting is 50 % and CT ratio is 400:5, then plug setting multiplier will be

A) 25A
B) 15A
C) 50A
D) 10A
Step-by-step calculation: 1. **Identify Given Data**: - Fault Current ($I_f$) = 2000 A - CT Ratio = 400:5 - Relay Setting (Plug Setting) = 50% (or 0.5) 2. **Calculate Secondary Fault Current**: The current flowing through the relay is the fault current scaled down by the CT ratio. Secondary Fault Current = $\frac{\text{Fault Current}}{\text{CT Ratio}} = \frac{2000}{400/5} = \frac{2000 \times 5}{400} = 25\text{ A}$. 3. **Calculate Relay Pick-up Current**: The pick-up current is the current at which the relay is set to operate. It is the product of the CT secondary rated current and the plug setting. Relay Pick-up Current = $\text{CT Secondary Current} \times \text{Relay Setting} = 5\text{ A} \times 0.5 = 2.5\text{ A}$. 4. **Calculate Plug Setting Multiplier (PSM)**: PSM is the ratio of the actual secondary fault current to the relay pick-up current. $\text{PSM} = \frac{\text{Secondary Fault Current}}{\text{Relay Pick-up Current}} = \frac{25\text{ A}}{2.5\text{ A}} = 10$. **Analysis of Options**: There is a discrepancy in the provided options. The calculated PSM is a dimensionless multiplier (10). However, the options are listed with 'A' (Amperes). If the question asks for the PSM, the answer is 10. If the options are intended to be the PSM value, option (d) is 10. However, looking at the options provided in the prompt (a: 25A, b: 15A, c: 50A, d: 10A), it appears there may be a typo in the units of the options. Based on the numerical result of the PSM calculation, the value is 10. *Correction/Observation*: In many competitive exams, if the options are listed as 'A' but the question asks for PSM, the numerical value is what matters. However, if we check the calculation again: $2000 / (400/5 * 0.5) = 2000 / 40 = 50$. Let's re-evaluate: $\text{PSM} = \frac{I_f}{\text{CT Ratio} \times \text{Relay Setting}} = \frac{2000}{(400/5) \times 0.5} = \frac{2000}{80 \times 0.5} = \frac{2000}{40} = 50$. Therefore, the PSM is 50. Option (c) matches this numerical value.
MES Jr. Grade • 2024 • Paper-II

An under-excited alternator operates at :

A) lagging power factor
B) leading power factor
C) unity power factor
D) leading or unity power factor
In a synchronous alternator, the excitation refers to the DC current supplied to the field winding. The state of excitation determines the reactive power exchange between the alternator and the grid: 1. **Under-excitation**: When the field current is low, the alternator cannot produce enough internal magnetic flux to maintain the terminal voltage. To compensate for this deficit, the alternator absorbs reactive power from the grid. This occurs when the load is inductive, meaning the alternator operates at a **lagging power factor**. 2. **Over-excitation**: When the field current is high, the alternator produces excess reactive power and supplies it to the grid. This occurs when the load is capacitive, meaning the alternator operates at a **leading power factor**. 3. **Normal excitation**: The alternator operates at **unity power factor**, where it neither absorbs nor supplies reactive power. Therefore, an under-excited alternator operates at a lagging power factor to draw the necessary reactive power from the system to maintain its magnetic field.
MES Jr. Grade • 2024 • Paper-II

A 6-poles synchronous motor is supplied by a 50 Hz, 440 V supply. At what speed the motor does run?

A) 750 rp.m.
B) 1000 rp.m.
C) 1500 rp.m.
D) 3000 rp.m.
For a synchronous motor, the running speed equals the synchronous speed: Ns = 120f / P. Here f = 50 Hz and P = 6 poles, so Ns = (120 × 50) / 6 = 1000 rpm. Therefore the correct option is b. However, since the question asks for a 6-pole synchronous motor, the motor runs at 1000 rpm, not 750, 1500, or 3000 rpm. Option a (750 rpm) corresponds to an 8-pole machine at 50 Hz, option c (1500 rpm) corresponds to a 4-pole machine, and option d (3000 rpm) corresponds to a 2-pole machine.
MES Jr. Grade • 2024 • Paper-II

What is incorrect statement about a power transformer?

A) It is designed to have maximum efficiency at or near full load
B) It is designed to have considerably greater leakage reactance
C) It isolates the generating plant from the transmission line electrically
D) It is designed to have maximum efficiency at or near half load
To determine the incorrect statement, let's analyze the characteristics of a power transformer: 1. **Efficiency and Loading (Options a and d):** Power transformers are used in transmission networks and are typically operated at or near their rated capacity (full load) for long periods. Therefore, they are specifically designed to achieve maximum efficiency at or near full load to minimize energy losses during bulk power transfer. Statement (a) is correct, and statement (d) is incorrect. 2. **Leakage Reactance (Option b):** Power transformers are designed to have a higher leakage reactance compared to distribution transformers. This is necessary to limit the short-circuit currents that can occur during faults in the high-voltage transmission system, protecting the equipment from catastrophic failure. Statement (b) is correct. 3. **Electrical Isolation (Option c):** One of the primary functions of a transformer is to provide galvanic isolation between the primary (generating plant) and secondary (transmission line) circuits, while still allowing the transfer of energy via electromagnetic induction. Statement (c) is correct. Since the question asks for the INCORRECT statement, option (d) is the right choice.
MES Jr. Grade • 2024 • Paper-II

Which of the following DC generators at load condition offers poorest voltage regulation?

A) Cumulative compounded generator
B) Series generator
C) Shunt generator
D) Differential compounded generator
Voltage regulation is a measure of the change in terminal voltage from no-load to full-load. A 'poor' voltage regulation in the context of DC generators typically refers to a significant drop in voltage as load increases. 1. **Shunt Generator (c):** The terminal voltage drops slightly due to armature resistance (IR drop) and armature reaction. It has moderate regulation. 2. **Series Generator (b):** The terminal voltage actually increases as the load increases because the load current increases the field flux. This is 'rising' regulation. 3. **Cumulative Compounded Generator (a):** The series field aids the shunt field. Depending on the design, it can be constant-voltage, under-compounded (slight drop), or over-compounded (slight rise). It generally offers the best (most stable) regulation. 4. **Differential Compounded Generator (d):** In this machine, the series field opposes the shunt field. As the load current increases, the series field flux subtracts from the shunt field flux, causing the terminal voltage to drop sharply. Because the voltage decreases rapidly with an increase in load, it exhibits the poorest (most severe) voltage drop, making it the correct answer.
MES Jr. Grade • 2024 • Paper-II

What will be the transfer function of the circuit shown below? Where, τ = RC

A) sτ
B) 1/(sτ)
C) sτ / (sτ + 1)
D) 1 / (sτ + 1)
For a standard RC circuit with the output taken across the capacitor, the transfer function is obtained from the impedance divider: Z_C = 1/(sC) Vout/Vin = Z_C / (R + Z_C) = [1/(sC)] / [R + 1/(sC)] = 1/(1 + sRC) Since τ = RC, the transfer function becomes: H(s) = 1/(sτ + 1) So option d is correct. Why the others are incorrect: - a) sτ: this is not the transfer function of a first-order RC low-pass circuit; it grows with frequency and does not match the capacitor-output divider. - b) 1/(sτ): this is an ideal integrator form, not the actual RC circuit transfer function. - c) sτ/(sτ + 1): this is the transfer function of an RC high-pass circuit (output across the resistor), not the capacitor-output case here.
MES Jr. Grade • 2024 • Paper-II

The hysteresis power loss in a transformer does not depend upon

A) applied voltage
B) applied frequency
C) transformer oil
D) material of the transformer core
Hysteresis loss occurs due to the friction between magnetic domains as they align and realign with the alternating magnetic field in the core. The formula for hysteresis power loss is given by: P_h = η * B_max^n * f * V, where η is the Steinmetz coefficient, B_max is the maximum flux density, f is the frequency, and V is the volume of the core material. 1. Applied Voltage (Option a): The maximum flux density B_max is directly proportional to the applied voltage (V ≈ 4.44 * f * N * Φ_max). Therefore, hysteresis loss depends on the applied voltage. 2. Applied Frequency (Option b): As seen in the formula, P_h is directly proportional to the frequency (f). 3. Material of the transformer core (Option d): The Steinmetz coefficient (η) depends on the grade of the core material (e.g., Cold Rolled Grain Oriented - CRGO steel). Better materials have smaller hysteresis loops and lower losses. 4. Transformer Oil (Option c): Transformer oil is used for insulation and cooling purposes. It does not participate in the magnetic flux cycle or the domain switching process within the core; therefore, it has no effect on hysteresis loss.
MES Jr. Grade • 2024 • Paper-II

In pumped storage

A) power is produced by means of pumps
B) water is stored by pumping to high pressures
C) downstream water is pumped up-stream during off load periods
D) water is recirculated through turbine
Pumped Storage Hydropower (PSH) acts as a giant battery for the electrical grid. It consists of two reservoirs at different elevations. 1. During 'off-peak' or 'off-load' periods (when electricity demand is low and prices are cheap), surplus energy from the grid is used to power pumps that move water from the lower (downstream) reservoir to the upper (upstream) reservoir. This stores energy as potential energy. 2. During 'peak' periods (when demand is high), the stored water is released from the upper reservoir back down to the lower reservoir through turbines to generate electricity. Analysis of options: - Option (a) is incorrect because power is produced by turbines, not pumps. Pumps consume power. - Option (b) is incorrect because water is stored by increasing its potential energy (elevation/head), not by compressing it to high pressures. - Option (c) is correct as it accurately describes the energy storage phase of the cycle. - Option (d) is partially true in a general sense, but 'recirculated through turbine' is imprecise; water is pumped up by a pump and released down through a turbine.
MES Jr. Grade • 2024 • Paper-II

As compared to closed loop system, an open loop system is

A) more stable as well as more accurate
B) less stable as well as less accurate
C) more stable but less accurate
D) less stable but more accurate
To determine the correct answer, we must compare the fundamental characteristics of Open-Loop and Closed-Loop control systems: 1. **Stability**: Open-loop systems are generally more stable. This is because they do not utilize feedback. In closed-loop systems, the feedback loop can potentially introduce instability (oscillations) if the gain is too high or if there are significant phase shifts in the system, leading to a positive feedback condition. 2. **Accuracy**: Closed-loop systems are significantly more accurate. Because they monitor the output and compare it with the desired reference (error detection), they can automatically correct for disturbances and internal parameter variations. An open-loop system has no way to detect if the output has deviated from the desired value and cannot correct itself, making it less accurate. Comparing the two: - Open Loop: High Stability, Low Accuracy. - Closed Loop: Potential for Instability, High Accuracy. Therefore, an open-loop system is more stable but less accurate than a closed-loop system.
MES Jr. Grade • 2024 • Paper-II

The diversity factor of a specific group of electrical consumers is

A) always greater than 1
B) always less than 1
C) may be less or greater than 1
D) may be higher than 100
The Diversity Factor is a fundamental concept in power system planning and distribution. It is defined as the ratio of the sum of the individual maximum demands of the various subdivisions of a system to the maximum demand of the entire system. Formula: Diversity Factor = (Sum of Individual Maximum Demands) / (Maximum Demand of the Whole System) Reasoning: 1. Individual maximum demands occur at different times for different consumers. For example, a residential consumer might peak in the evening, while a commercial consumer peaks during the day. 2. Because these peaks do not coincide perfectly, the maximum demand on the overall system (the denominator) will always be less than the arithmetic sum of the individual peaks (the numerator). 3. Since the numerator is always greater than the denominator, the resulting ratio is always greater than 1. Analysis of options: - Option (a) is correct because the sum of individual peaks is always higher than the simultaneous peak of the group. - Option (b) is incorrect because a value less than 1 would imply that the system peak is higher than the sum of its parts, which is physically impossible. - Option (c) is incorrect because it cannot be less than 1. - Option (d) is incorrect because while it can be higher than 1, it is typically a small number (e.g., 1.2 to 2.0) and is not 'defined' by being higher than 100.
MES Jr. Grade • 2024 • Paper-II

AC network analyzer is used to solve the problem of

A) load-flow
B) load-flow and short-circuit
C) load-flow and stability
D) load-flow, short-circuit, and stability
An AC network analyzer is a specialized analog computer designed to simulate the behavior of electrical power systems. It uses operational amplifiers, resistors, and capacitors to model the physical properties of a power network. Because it mimics the actual electrical network, it can be used to perform several types of analyses: 1. Load-flow analysis: By setting the inputs to represent generators and loads, the analyzer determines the voltage magnitudes and phase angles at all buses. 2. Short-circuit analysis: By introducing a low-impedance path (simulating a fault), the analyzer can determine the fault currents and voltage drops across the system. 3. Stability analysis: By simulating changes in load or generation over time (transient behavior), it can be used to study the dynamic stability of the system. Therefore, it is a versatile tool capable of solving all three problems mentioned.
MES Jr. Grade • 2024 • Paper-II

A phase-lag compensation will

A) improve relative stability
B) increase the speed of response
C) increase bandwidth
D) increase overshoot
A phase-lag compensator adds negative phase and is mainly used to improve steady-state accuracy by increasing low-frequency gain. It generally reduces bandwidth and slows the response, but it can improve relative stability by increasing the gain margin/phase margin characteristics in the low-frequency region. Hence, the correct option is (a) improve relative stability. Why the others are incorrect: - (b) increase the speed of response: false. Lag compensation usually makes the system slower, not faster. - (c) increase bandwidth: false. Lag compensation typically decreases bandwidth. - (d) increase overshoot: not the intended primary effect. Overshoot may change depending on design, but the standard effect of lag compensation is improved steady-state performance and relative stability, not increased overshoot.
MES Jr. Grade • 2024 • Paper-II

Which type of fault is most frequent fault on a transmission line?

A) Single-line to ground fault
B) Double-line to ground fault
C) Three-phase to ground fault
D) Three-phase short circuit fault
In power system analysis, faults are categorized based on the number of phases involved and whether they are connected to the ground. 1. **Single-Line-to-Ground (SLG) Fault**: This occurs when one of the three phases comes into contact with the ground or a neutral wire. This is the most common type of fault (occurring roughly 70-80% of the time) due to factors such as lightning strikes, tree branches touching a single conductor, or insulator failure. 2. **Double-Line-to-Ground (DLG) Fault**: This occurs when two phases are shorted together and also touch the ground. This is less frequent than SLG faults. 3. **Three-Phase-to-Ground (3LG) Fault**: This occurs when all three phases touch the ground. While this is the most severe fault in terms of current magnitude, it is the rarest occurrence. 4. **Three-Phase Short Circuit (L-L-L) Fault**: This is a symmetrical fault where all three phases are shorted together without necessarily involving the ground. Like the 3LG fault, it is very rare. Therefore, based on statistical occurrence in transmission networks, the Single-line to ground fault is the most frequent.
MES Jr. Grade • 2024 • Paper-II

The series field winding of a series wound DC machine generally

A) connected in parallel with the armature winding of the machine
B) made of fine conductor wire
C) made of large number of turns of wire
D) carry same amount of current as armature current
In a series wound DC machine, the field winding is connected in series with the armature winding. By the fundamental laws of series circuits, the same current flows through all components connected in series. Therefore, the full load current flowing through the armature must also flow through the series field winding. Analysis of other options: - Option (a) is incorrect because if the field winding were in parallel, it would be a shunt wound machine, not a series wound machine. - Option (b) is incorrect because the series field must carry the full armature current (which is typically high). Fine wire would have high resistance and would burn out due to excessive I²R losses. - Option (c) is incorrect because a large number of turns would increase the resistance and the voltage drop across the field winding. Series fields are typically made of a few turns of thick wire to keep resistance low while handling high current.
MES Jr. Grade • 2024 • Paper-II

Under which condition usually circuit breakers operate?

A) Transient state of short-circuit current
B) Sub-transient state of short-circuit current
C) Steady state of short-circuit current
D) When there is no DC current component
When a short circuit occurs in a power system, the fault current consists of an AC component and a DC offset. The current behavior is divided into three stages: 1. Sub-transient period (first few cycles), 2. Transient period, and 3. Steady-state period. The sub-transient current is the highest magnitude current because the reactance of the machine is at its minimum during this initial phase. Circuit breakers are designed to detect the fault and operate almost instantaneously to isolate the fault. Since the relaying and tripping process takes a finite amount of time (typically a few cycles), the breaker usually interrupts the current during the sub-transient or early transient phase. Specifically, for the purpose of calculating the 'Interrupting Capacity' of a circuit breaker, the sub-transient current is the critical value considered because it represents the maximum stress the breaker must withstand. Therefore, circuit breakers typically operate during the sub-transient state of the short-circuit current.
MES Jr. Grade • 2024 • Paper-II

A transformer has negligible resistance and a pure reactance of 0.1. Its voltage regulation on full load with a leading pf angle of 30° leading is

A) -10%
B) 10%
C) 5%
D) -5%
For a transformer with negligible resistance, the approximate voltage regulation is VR ≈ R_eq cosφ ± X_eq sinφ Since resistance is negligible, R_eq = 0, so VR ≈ ± X_eq sinφ Given X_eq = 0.1 pu and the load power factor is 30° leading, so φ = 30° and sin30° = 0.5. For a leading power factor, the reactance term causes a voltage rise, so regulation is negative: VR = -0.1 × 0.5 = -0.05 = -5% Hence the correct option is d) -5%. Why others are incorrect: - a) -10%: would require either a larger reactance or a larger angle; not consistent with 0.1 pu and 30°. - b) 10%: wrong magnitude and wrong sign. - c) 5%: correct magnitude but wrong sign; leading pf gives negative regulation.
MES Jr. Grade • 2024 • Paper-II

Then negative phase sequence in a three phase synchronous motor exists when the motor is

A) under loaded
B) overloaded
C) supplied with unbalanced voltage
D) hot
In a three-phase system, the concept of sequence components (Positive, Negative, and Zero sequence) is used to analyze unbalanced conditions. 1. **Positive Sequence**: This occurs when the three phases are balanced and have the same phase sequence as the motor's design. It produces a rotating magnetic field that rotates in the intended direction of the motor. 2. **Negative Sequence**: This occurs when the phase sequence is reversed relative to the positive sequence. In a synchronous motor, a negative sequence component is created specifically when the supply voltages are unbalanced (i.e., the magnitudes of the voltages are different or the phase angles between them are not exactly 120 degrees). 3. **Effect**: The negative sequence field rotates in the opposite direction to the rotor's rotation. This induces double-frequency currents in the rotor, leading to overheating and torque pulsations. Analysis of options: - (a) Under loaded: Loading conditions affect the current magnitude and power factor, but not the phase sequence of the supply voltage. - (b) Overloaded: Overloading leads to increased current and potential overheating, but it does not create a negative phase sequence unless the overload causes a phase failure or severe voltage drop in one phase. - (c) Supplied with unbalanced voltage: This is the direct cause of negative sequence components according to Fortescue's Theorem of Symmetrical Components. - (d) Hot: Temperature is a result of losses (including those from negative sequence currents), not a cause of the sequence itself.
MES Jr. Grade • 2024 • Paper-II

The corona loss in a three-phase transmission line does not depend upon the parameter

A) thickness of the conductor
B) power frequency
C) distance between the conductors
D) phase-sequence
Corona loss in a transmission line is the power loss caused by the ionization of air surrounding the conductor when the electric field intensity exceeds the dielectric strength of air. The formula for corona power loss (Peek's formula) is given by: P = (24.1) * f * m * d * (V - Vc)^2 * 10^-5 kW/km, where f is the power frequency, m is the number of phases, d is the diameter of the conductor, and V is the operating voltage. 1. Thickness of the conductor (Option a): The diameter (d) of the conductor directly affects the electric field intensity at the surface. A thicker conductor reduces the field intensity, thereby affecting corona loss. 2. Power frequency (Option b): As seen in the formula, corona loss is directly proportional to the frequency (f) of the AC supply. 3. Distance between the conductors (Option c): The spacing between conductors affects the critical disruptive voltage (Vc). If conductors are closer, the electric field is modified, influencing when corona begins and the magnitude of the loss. 4. Phase-sequence (Option d): The phase sequence (e.g., R-Y-B or R-B-Y) refers to the order in which the voltages reach their peak values in a three-phase system. It has no physical impact on the electric field intensity around an individual conductor or the ionization of the surrounding air. Therefore, corona loss is independent of the phase sequence.
Page 56
← Prev Next →